L-24
4 Programming
4.7 Error Status
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
•For FX3U, FX3UC Series PLC
2. Program Example 1 (For FX3G, FX3U, FX3UC Series PLC)
*1. "1st" for the FX3G PLC.
Error status in the 1st analog special adapter
b6 = OFF (hardware error)
Error status in the 1st analog special adapter
b7 = OFF (communication data error)
M8002
Initial pulse
RST D8268.6
RST D8268.7
Y000
M0
M1
M2
M3
M4
M5
M6
M7
Y001
Y002
Y003
Y004
EEPROM error in 3rd
*1
adapter
Y005
Y006
Y007
Averaging time setting error in 3rd
*1
adapter
TC-ADP hardware error in 3rd
*1
adapter
TC-ADP communication data error
in the 3rd
*1
adapter
The temperature measurement data
of channel 1 is outside the specified
range, or disconnection is detected.
The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
The temperature measurement data
of channel 3 is outside the specified
range, or disconnection is detected.
The temperature measurement data
of channel 4 is outside the specified
range, or disconnection is detected.
M8000
MOV
D8288 K4M0